Note: Parameters identified as “Power 1” are associated with the controlled load (light, dimmer or receptacle depending on the host device). For "Power 2" parameters and additional Power 1 parameters, please download the Swidget Z-Wave Universal Insert Configuration guide.
Power 1 High Entry Level
Parameter: 1 (0x0001)
Description: Used to set the power value for Power 1 that indicates entry into a Power 1 High state.
Range: 0 – 2400 Watts
Units: Watts
Default: 2400 (0x0960)
Power 1 Low Entry Level
Parameter: 2 (0x0002)
Description: Used to set the power value for Power 1 that indicates entry into a Power 1 Low power state.
Range: 0 – 2400 Watts
Units: Watts
Default: 0 (0x0000)
Power 1 High Exit Level
Parameter: 3 (0x0003)
Description: Used to set the power value for Power 1 that indicates exit from a Power 1 High state.
Range: 0 – 2400 Watts
Units: Watts
Default: 2400 (0x0960)
Power 1 Low Exit Level
Parameter: 4 (0x0004)
Description: Used to set the power value for Power 1 that indicates exit from a Power 1 Low power state.
Range: 0 – 2400 Watts
Units: Watts
Default: 0 (0x0000)
Power 1 High Delay
Parameter: 5 (0x0005)
Description: Used to set the time duration for Power 1 High state changes.
Range: 0 – 65535 Seconds
Units: Seconds
Default: 0
Power 1 Low Delay
Parameter: 6 (0x0006)
Description: Used to set the time duration for Power 1 Low state changes.
Range: 0 – 65535 Seconds
Units: Seconds
Default: 0 (0x0000)
Power 1 Periodic Report
Parameter: 7 (0x0007)
Description: Used to set the time in seconds for Power 1 kWh METER REPORTs to the Lifeline.
Range: 0 to 65535 Seconds
Units: Seconds
Default: 3600 (1 hour)
Power 1 High Entry SET Value
Parameter: 10 (0x000A)
Description: BASIC SET value sent to associated nodes on entry into Power 1 High state.
Range: 0 – 255 (Note: 100 - 254 is interpreted as 255)
Units: BASIC CC SET LEVEL
Default: 255 - turn on associated devices
Power 1 High Exit SET Value
Parameter: 11 (0x000B)
Description: BASIC SET value sent to associated nodes on exit from Power 1 High state.
Range: 0 – 255 (Note: 100 - 254 is interpreted as 255)
Units: BASIC CC SET LEVEL
Default: 0 - turn off associated devices
Power 1 Low Entry SET Value
Parameter: 12 (0x000C)
Description: BASIC SET value sent to associated nodes on entry into Power 1 Low state.
Range: 0 – 255 (Note: 100 - 254 is interpreted as 255)
Units: BASIC CC SET LEVEL
Default: 255 - turn on associated devices
Power 1 Low Exit SET Value
Parameter: 13 (0x000D)
Description: BASIC SET value sent to associated nodes on exit from Power 1 Low state.
Range: 0 – 255 (Note: 100 - 254 is interpreted as 255)
Units: BASIC CC SET LEVEL
Default: 0 - turn off associated devices